In the CRBasic program, set up multiple data tables using the DataTable() instruction. In each table, specify the desired output interval using the DataInterval() instruction.
For example, the following three table definitions could be included in a program to store values once a day, once an hour, and every minute.
DataTable (Daily,1,1000)
DataInterval (0,24,Hr,10)
Minimum (1,batt_volt,FP2,0,False)
Sample (1,PTemp,FP2)
EndTable
DataTable (Hourly,1,1000)
DataInterval (0,1,Hr,10)
Minimum (1,batt_volt,FP2,0,False)
Sample (1,PTemp,FP2)
EndTable
DataTable (OneMinute,1,1000)
DataInterval (0,1,Min,10)
Minimum (1,batt_volt,FP2,0,False)
Sample (1,PTemp,FP2)
EndTable
Note: The shortest interval at which the CR200X-series dataloggers can store data is once every minute.